BE1-GPS100
Equipment › Equipment for alternators › Equipment for boiler houses / power plants › Protective Relays › BE1-GPS100
BE1-GPS100
ADVANTAGES
- BESTlogic provides the user with very high flexibility in configuring a protection and control system.
- Substantial functionality in a small package, useful where space is very limited but high functionality is needed.
- Programmable LCD display allows the relay to replace local indication and control functions, such as panel metering, alarm annunciation, and control switches.
- Provides optional separate ground current input for those applications where this is required.
- Three independent communication ports with protocol support allows integration with distributed control systems.
- Includes frequency tracking and voltage restrained overcurrent for backup and cogeneration applications.
BE1- GPS100 FEATURES
PROTECTION
- Phase and Neutral Instantaneous Overcurrent elements with settable time delay:
- Phase, Neutral, and Negative Sequence Time Overcurrent elements:.
- Phase overcurrent element includes capability of voltage restraint or voltage control.
- Negative sequence overcurrent element (46) includes algorithm for timing based on generator K factors or may use standard TOC curves..
- All U.S. and IEC timing curves plus user programmable curve.
- Phase Undervoltage and Overvoltage elements.
- Auxiliary Undervoltage and Overvoltage elements.
- Negative Sequence Overvoltage element:
- Four Under/Overfrequency elements.
- Forward/Reverse Power.
- Loss of Excitation (offset sloped VAR flow algorithm).
- Breaker Failure protection function: BF
- 4 general purpose logic timers: 62,162,262, 362
- Inadvertent energization protection
- 100% stator ground fault protection using auxiliary voltage elements for ground overvoltage and 3rd harmonic ground undervoltage
- Sync check and/or dead bus close supervision
- Programmable Logic using BESTlogic
- Two protection settings group controllable via relay logic, 43 Aux switches, and hardwired inputs. Setting group selection may control tripping logic.
- Fuse loss detection (60FL) protects against false trip due to loss of voltage sensing.
CONTROL
- Virtual breaker control switch-controllable from both HMI and com. Ports and four virtual selector switches-controllable from both HMI and com. ports, also communication port control of 101 and #43 switches allows for SCADA control of relay and breaker.
INSTRUMENTATION
- Real time A, B, C phase current, voltage; frequency; and derived neutral and negatyve sequence current and voltage. Real Time 3 phase Watts, VARs, and Power Factor.
REPORTS
- Current demands for phase, ground, and negatyve sequence currents, and forward and reverse Watts and VARs-magnitudes and time stamps are recorded for today’s peak, yesterday’s peak, and peak since reset.
- kWh and kVARh, forward and reverse
- Breaker operations counter and contact interruption duty. Breaker operate time also available.
FAULT RECORDING
- 255 event sequence of events report with I/O and alarm sub-reports
- Fault Reporting; 1 or 2 oscillography records per fault report
- 16 fault summary reports; two most recent Fault Summary Records saved to non-volative memory
- Total number of fault and oscillography records settable from 6 to 16
- Total of 240 cycles oscillography memory @ 12 samples/cycle
COMMUNICATION PORTS
- Three independent general purpose communication ports
- Front RS-232 ASCII communications
- Rear RS-232 ASCII communications
- Rear RS-485 ASCII, Modbus*, DNP*3.0, and TNP protocols
- IRIG-B time sync (unmodulated)
SELF TEST AND ALARM FUNCTIONS
- Relay fail, major alarm, and minor alarm LEDs, and fail-safe alarm output contact (closed or open) also extensive internal diagnostics monitor all internal functions of the relay.
- More than 20 additional alarm points - programmable for major or minor priority including:
- User defined logic state alarms that may be associated with any user specified relay logic state or relay protective element status.
- Phase current, and forward and reverse Watt and VAR demand alarm.
- Neutral and negative sequence unbalance demand alarms.
- Three breaker alarm points programmable for slow trip, interruption duty threshold, or operations counter.
- Trip circuit voltage and continuity monitor.
PROGRAMMABLE I/O
- Four programmable inputs.
- Five programmable outputs and one dedicated programmable alarm output.